CAT 3 4PR 
  CAT 3 6PR  
  CAT 5E 
  FTP CAT 5E 
  CAT 6E 
ANS/TIA/EIA 568 Category 5e
 
1) Construction
2) Pair Identification
Pair 1 Blue/White w/Co-extruded Blue Strip on White Single
Pair 2 Orange/White w/Co-extruded Orange Strip on White Single
Pair 3 Green/White w/Co-extruded Green Strip on White Single
Pair 4 Brown/White w/Co-extruded Brown Strip on White Single
Pair 5 Slate/White w/Co-extruded Slate Strip on White Single
Pair 6 Blue/Red w/Co-extruded Blue Strip on Red Single

3) Characteristics
Installation Temperature: 0℃ to 60℃ Operation Temperature: -20℃ to 60℃
Capacitance: 20pf/ft nominal
DC Resistance/Unbalance: 28.6 ohms/1000’Max/5% Max
Dielectric Breakdown: 2500 Volts DC Conductor to Conductor
Attenuation: ≤2.320•νfred + 0.238•fred 0.772≤fred≤16
Maximum Skew: 11ns@100 meters
Structural Return Loss: ≥12 1≤fred≤10
≥12 – 10 log(fred/0.772) 10≤fred≤16

4) Electric Performance
Frequency (MHz) Attenuation (dB/100m) Near End Cross Talk (dB) Structural ReturnLoss (dB)
EIA/TIA 568Category 3 EIA/TIA 568Category 3
0.772 6.8 43 NA
1.0 7.8 41 12
4.0 17.0 32 12
8.0 25.9 27 12
10.0 30.0 26 12
16.0 40.0 23 10
 
5) Approval:
UL:---------------------------CMX, CM, CATV, CL2, CMR
6) Jacket Color:  
Gray, White, Blue, Orange, Purple, Green, Red, Yellow, Black etc.  
   
7) Packing:  
 
 
 
 
All Right Reserved by YuJunCable.com TEL: +86-571-88386268 FAX: +86-571-88386278 Email:sales@yujuncable.com